3300AP Elevator System Comprehensive Technical Manual

Complete technical reference for Schindler 3300AP elevator control system. Includes Menu 10 functions, all status code meanings & troubleshooting, and key configuration parameters (CF/PA). Essential f

FELEVATOR7 min read
Read the article
3300AP Elevator System Comprehensive Technical Manual
The FELEVATOR journal

1. MENU Functions (Menu 10)

Code Display Function Description
101 [10/1] Sends a fatal error reset command to the ACVF and elevator control. Clears fatal errors related to pre-opening, association, KNE, KSE, KB/KB1 brake contacts, safety circuit, and PHSX bridging.
102 [10/2] Activates ACVF Open Loop Mode. Allows travel via Inspection or Recall control despite faults in motor encoder, KB/KB1 brake contacts, or ACVF/motor temperature sensors.
103 [10/3] Initiates GBP Reset Mode. Enables travel beyond KSE-U4 to reset overspeed governor contacts. Automatically activates/deactivates KFM mode (Maintenance/Test Travel Mode).
104 [10/4] Activates/Deactivates Installation Run Mode (persists after reset).Note: Requires reset after deactivation to resume normal operation.
105 [10/5] Enables/Disables Load Weighing (CLC) (0: Enable,1: Disable). Activates/Deactivates Key Switch function (IAB) (0: Activate,1: Take elevator Out-of-Service).
107 [10/7] Activates Enhanced Service Function (single-use only).
108 [10/9] Registers a Car Call.
109 [10/9] Registers a Hall Call.
110 [11/0] Issues Door Open command (doors will not auto-close). Issues Door Close command (doors will not auto-close).
111 [11/1] Remote Alarm Control Center command for remote elevator shutdown. Use Command 114 to return to service. Deactivates Earthquake Service (EB) (1: Deactivate).
112 [11/2] Initiates a Learning Run (hoistway position self-learning). Service Access Switch (Disable/Enable Remote Monitoring):0= Errors unfiltered & sent via remote monitoring (auto-resets to0after 30 min inactivity).1= Errors not sent via remote monitoring (auto-sets to1during maintenance).
113 [11/3] Activates/Deactivates Pre-torque Calibration (0: Activate). Useful for elevators like Schindler 3100.
114 [11/5] Deactivates Sprinkler Recovery Service (SR) (1: Deactivate).
115 [11/6] Sends a Remote GBP Reset Command.
116 [11/7] Next Call Command. Forces immediate TM call, aiding automatic configuration acceleration.Note: CGW is disabled.
117 [11/8] Used after TM device installation/replacement if TM communication fails (Refer to 5.4.24 ETM - Embedded Telemetry).
123 [12/8] COP Detection. Used after installing a new COP.
124 [12/9] Hall Call Detection & Node Scan (e.g., CF=00, LE=00, floor count).
125 [13/0] Confirms installed LMS is switch type (11: Switch Confirmed,01: Switch Not Confirmed).*Required only if switch-type LMS is installed. Not applicable to Schindler 3100/3300/5300.*
126 [12/6] Temporarily disables alarm filter for alarm testing. When active, alarms are not filtered even during car motion or open doors. Auto-resets to0after 30 seconds.
127 [13/5] Stops Alarm. Resets a pending alarm (COP alarm indicator).
128 [13/6] Overlay Detection (3/4). Must be performed during commissioning. Repeat if overlay is removed from the system.
136 [13/6_] Overlay Detection Result:[136_1]= Correct,[136_0]= Incorrect.
137 [13/7_] Overlay Reset. Resets the overlay box (same function as reset button on box). Must be executed after configuring CF=04, PA=01.
138 [13/8_] Emergency Car Lighting Detection/Calibration (SW³ V11).
139 [13/9_] Emergency Car Lighting Calibration (SW³ V11).
140 [14/0_] Stationary Load Auto-tuning (SW³ V9.8 Mid+ / Schindler 3600). HMI signs off stages; final display:0= Fail,1= Success.
141 [14/1_] Auto-tune Encoder Offset (SW³ V9.8 Mid+ / Schindler 3600). HMI signs off stages; final display:0= Fail,1= Success.
142 [14/2_] Auto-tune Dynamic Motor (SW³ V9.8 Mid+ / Schindler 3600). HMI signs off stages; final display:0= Fail,1= Success.
143 [14/3_] High Torque Trip (Available from V9.9, REACH drive only).
144 [14/4_] Note: Requires Recall activation. Press & hold DRH-U/D to open doors. Parameter deactivates upon DRH-U/D release.
145 [14/5_] CDD Detection (Available from V10). Activates detection for CDD.
146 [14/6_] ECM Calibration (Available from V10). Activates ECM calibration.
147 [14/7_] Note: Accessible only if Menu 190 is triggered.
148 [14/8_] ECM Clear Errors & Warnings (Available from V10). Clears: - Pop-up -4624 - ECM error/warning states.
149 [14/9_] Door Drive Detection (Available from V11). Removes detected door drives from EC. Execute with all drives disconnected. Reconnect drives afterward for auto-recognition (Varidor 15 only).
150 [15/0_] KB/KB1 Monitoring Bypass (Var). Temporarily disables KB/KB1 monitoring during Recall/Inspection runs only. State not reset-proof. Monitoring restarts on elevator run command (Variodyn).
151 [16/1_] Motor Overtemp Bypass (Var). Temporarily disables motor overtemp monitoring during Recall/Inspection runs only. If motor overtemp activates during bypass, elevator waits for timer expiry before bypass. State not reset-proof. Monitoring restarts on elevator run command.
152 [16/2_] Door Lock Command. Sends lock command to available doors. Primarily used to close safety circuit during TSD21 hardware egress procedures.
153 [19/0_] Enable Single STM Config Change (Available from V10). Allows modification of CF 28 PA 6.9 parameters and Menu 145 for 300 seconds when enabled.
199 [19/9] Call Simulator (Available from V10). Technician initiates calls with configurable behavior. Input hex code inXYYZZformat:
X: Call Mode:
0=Stop Sim,1=Hall Calls (random floor/side),2=Car Calls (random floor),3=Hall & Car Calls
Y: Call Delay (sec):(Modes 1,2,3) or Delay between calls (Modes 4,5,6).0=Stop.
ZZ: # Trips (x100 units):0=Infinite.
Controller continues simulation after SW reset until trips complete. Infinite sims terminate on SW reset. Includes power cycles (±100 trip error). Calls unrestricted. Menu displays current mode & remaining trips (hex, x100).
Example:2100A= Car Call sim running, 16s delay, 1000 trips remaining.

2. Elevator Status Codes

Code Status Description Meaning Action/Troubleshooting
00 Out of service operation Locked Check Menu 10 > 108; Reset SAB via Menu 10 > 114
01 Passenger travel operation Normal -
02 Independent operation, reservation control Independent Dependent on car calls
03 Fire operation activated after trigger Fire Operation -
04 Firefighter operation activated after trigger Firefighter Operation -
05 Emergency power operation without load monitoring Emergency Power -
06 Earthquake service activated after detection Earthquake Operation -
07 Priority patient evacuation (like Independent) Emergency Medical Tech -
08 Sprinkler service activated (building sprinklers active) Sprinkler Operation -
09 Water detected in pit Water in Pit -
10 Attended operation (controlled by car attendant) Attendant Mode -
11 Normal operation with load monitoring disabled Weighing Disabled -
12 Evacuation mode Evacuation Mode -
13 Car at full load capacity Full Load -
14 No operation after emergency stop with trapped passengers Stop in Car -
15 No operation due to stop in car firefighter mode Firefighter Stop in Car -
16 Car overload condition detected Car Overload -
17 Locked due to invalid config data (e.g., missing/defective SIM) Invalid Config Data -
18 Hoistway data error/missing Hoistway Image Error -
19 LMS config invalid (requires recalibration) LMS Error -
20 Drive parameter setting error Driver Setting Error -
21 STM ribbon monitoring fault STM Monitoring Fault -
22 Service technician active Maintenance Mode -
23 Installation travel active Installation Mode -
24 Running in configuration mode (HMI activated) Configuration Mode -
25 Recall travel control from machine room or LDU Machine Room Inspection -
54 Inspection travel controlled from car top Top of Car Inspection -
55 Inspection travel controlled from inside car In-Car Inspection -
56 Hoistway access control active Top Landing Access -
57 Test travel active Test Run -
58 V15 Door Drive in test mode Test Mode -
59 Learning run active (measuring hoistway) Learning Travel -
60 Traveling to position for top access Inspection Prep Travel -
61 Overspeed governor switch not reset Gov. Reset Travel Reset via Menu 125
65 Bionic7 pit box incorrect operation Pit Maintenance Mode -
70 System recovery in progress Recovery -
71 Motor thermistor fault/unplugged Temp. Recovery -
72 Car position calibration in progress Position Recovery -
73 Door position calibration in progress Door Pos. Recovery -
74 Backup power calibration in progress Backup Pwr Recovery -
75 Safety loop open (common: tension pulley switch) Safety Loop Open -
80 Emergency Stop pressed (analyze safety circuit/logic) E-Stop Active -
81 Top of Car E-Stop active Top Car E-Stop -
82 Machine Room E-Stop active M.Room E-Stop -
83 Top Landing E-Stop active Top Landing E-Stop -
84 Pit E-Stop active Pit E-Stop -
85 BTM persistent fatal error BTM Error Reset via Menu 164
86 Remote monitoring disabled Remote Check Disabled -
87 System starting / SKC fuse blown / version mismatch Starting -
88 Power failure Power Cut -
89 Minor fault (Check E/F fault codes) Minor Failure -
90 Critical fault (Check F/P fault codes) Critical Fault -

3. Key Configuration Notes

  • Door Timing (Forced Close):SetCF03 PA21 = 0.

  • Encoder Setup:CF16 PA14(Encoder Type:0or1, Default=1).

  • Motor Phase Reversal:CF16 PA15(Phase Sequence:0or1, Default=1).

  • Fire Service/Lock Configuration:

    • Fire Operation (X3):CF40 VL01 PA21 = 99

    • Fire Recall (X3):CF40 VL02 PA22 = 56

    • Lockout (X4):CF40 VL02 PA21 = 49(Lockout configurable above 2F)

  • Balance Factor Measurement (Menu 20 Command 42):

    1. Send elevator to top floor (doors open).

    2. Load car with 50% rated load.

    3. Press OK (doors close, car runs to bottom).

    4. At bottom (doors remain closed), last 2 HMI digits show DOWN current. Press OK.

    5. After stop, last 2 HMI digits show average UP current.

    6. UP/DOWN currents should be equal. Adjust counterweight:

      • Increase if UP current higher.

      • Decrease if DOWN current higher.