FELEVATOR

The FELEVATOR journal

CO SC 1 Learning Run & Load Weighing Configuration

Execute CO SC 1 learning run and configure load weighing system including zero load, reference load, and overload verification.

FELEVATOR4 min read
Read the article
CO SC 1 Learning Run & Load Weighing Configuration
The FELEVATOR journal

1. LeArning to run

1.1 Start the learning process

► HMI: Freeze NodeTree

HMI: Commands → FreezeNodeTree → OK.

► Ensure:

– Installers remain in front of the control cabinet.

– The car must be between the top and bottom hall stations.

► AS.HMI: Start Learning Operation.

HMI: Commands → Special Trips → JLF → OK.

► AS.SCPOW: Set JRH/JEM to NORMAL.

► HMI: Stop Installation and Running MOF.

HMI: Commands → Special Trips → MOF → OFF → OK.

The learning run has begun. During the learning run, the HMI displays the floor number for the corresponding location.

CO SC 1 Learning Run & Load Weighing Configuration

The learning process automatically stops in AC GSI self-learning mode.

► If the HMI displays "TMMB": Perform the configuration of the traction media.

If the elevator is equipped with a traction medium, it will be locked on the first floor hall, awaiting STM setup.

CO SC 1 Learning Run & Load Weighing Configuration

► If the HMI displays "BESC": Configure the emergency stop counter for the brake.

- If the elevator has the emergency stop counter function set, the elevator will be locked, awaiting its configuration.

CO SC 1 Learning Run & Load Weighing Configuration


1.2 Final check during learning operation

Learning process complete. HMI display:

CO SC 1 Learning Run & Load Weighing Configuration

► AS.HMI: Call the elevator from the car at both entrances to each floor.

HMI: Commands → Car call → Floor → Entry side → OK.


2. Weighing configuration

The commissioning steps described in this chapter apply to the KL66 load cell installed on the car and the AC FMW load cell installed at a fixed point.

► Ensure all counterweight blocks are added, as shown in the installation manual.

► Ensure the guide rails are correctly adjusted.

► Ensure the sliding or roller guide shoes are correctly adjusted within allowable tolerances. Installation must be performed according to the civil engineering drawings.

► If the load cell AC FMW is installed at a fixed point:

- AS.SCMAIN.LMS: Insert the load cell plug into the FIMO.

CO SC 1 Learning Run & Load Weighing Configuration

1      FIMO box                            2      Sensor - FIMO box cable

3      AC FMW load cell            4      Rope end plate

► AS: Set the following switches to ON:

JH SIS SIL

2.1 0 kg configuration

► Ensure the car is empty.

► AS.HMI: Move the car to the floor where the calibration weights are located.

► AS.HMI: Activate the load cell LMS.

HMI: Commands → LM Disable → Enable → OK.

► AS.HMI: Open the car door.

HMI: Command → Door → Side 1 or 2 → Open → OK.

► After the car door is fully open:

AS.SCPOW: Set JRH/JEM to INSPECTION.

– Keep the car door open during calibration.

► AS.HMI: Obtain the zero-load reference point.

HMI: Commands → LM Commiss CLC → Zero Load Calibration → OK.

The controller reads the load cell output and sets the zero-load point for the empty car.

► AS.HMI: Wait until the HMI displays "Success".


2.2 Configure reference load

Car: Place the calibration weights into the car.

- Car load 40...100%.

► AS.HMI: Input reference load

HMI: Commands → LM Commiss CLC (Weighing Calibration CLC)

→ Ref Load Cal (Reference Load Calibration).

- The HMI displays the input screen for the reference load value in kg.

- Set the new reference load value → OK.

- The controller reads the load cell output and sets the reference load point using the calibration weights.

► HMI: Wait until the HMI displays "Success".

► Car: Remove the load from the car.

► Car: Ensure the car is empty.

► AS.HMI: Start KFM and stop outbound calls.

HMI: Command → Special trips → KFM → ON → OK

► AS.SCPOW: Set JRH/JEM to NORMAL.

– Car doors close.

► AS.HMI: Begin collecting floor-related zero-load calibration values. This is related to the compensation chain.

HMI: Command → LM Compmiss CLC → FloorAdjTravel → Compensation chain → Yes/No → OK

– The elevator begins calibration runs for each floor to obtain the zero-load value for each floor.

– The HMI displays “FloorAdjTravel = Success” and the maximum deviation value, i.e., the floor with the maximum deviation.

► AS.HMI: Press the ESC button to stop CLC commissioning.

► AS.HMI: Reads weighing parameter values ​​and records them on the controller label (parameter change record).

HMI: Status → LM Calib Data → OK.

Zero Load Frequency:

– Zero Load Frequency 1 (Hz)

– Zero Load Frequency 2 (Hz).

Reference Load Frequency:

– Reference Load (kg)

– Reference Load Frequency 1 (Hz)

– Reference Load Frequency 2 (Hz).

► AS.HMI: Stops KFM and starts outbound calls.

HMI: Command → Special Trips → KFM → OFF → OK.


2.3 Configure minimum load

Minimum Load Adjustment

The weighing system's nonlinearity and insufficient resolution prevent it from accurately identifying smaller loads. This can disable in-car calls or cause standby power management malfunctions. The next step is to adjust the control unit's recognition threshold to 50 kg to eliminate these limitations.

► AS.HMI: Activate reserved service mode.

HMI: Commands → Services → Service JRV → ON → OK.

► Car: Place a 50 kg load in the center of the car.

► AS.HMI: Access load and frequency.

HMI: Status → LM Load and frequency

► HMI: Enter the in-car call for each floor.

HMI: ESC+OK → Floor → Entry side → OK.

► Record the load value displayed when the elevator stops at each floor.

► Select the smaller recorded value.

► Store the smaller value.

HMI: Parameter → Car → Minimal Load → OK.


2.4 Overload Inspection

► Car: Loads a load equivalent to 110% of the car's load capacity in the car.

► AS.HMI: Ensures that the L-X indication is displayed.

CO SC 1 Learning Run & Load Weighing Configuration

► Car: Remove load from the car.

► AS.HMI: Check if "L-X" has changed to "Normal".

► AS.HMI: Stop the reserved service mode.

HMI: Commands → Services → Service JRV → OFF → OK.

Working on a similar project?

Send a part number or photo. Our team can help with the next step.

Ask our team
Image detail

Share the part number, product photo, elevator model, and quantity. Our team will help confirm compatibility, availability, and shipping.

Contact FELEVATOR

Send your requirements to our elevator parts team.